Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Underground
Permit Number - TC-COM-0525-00980
Inspection Description - COT - LCEL - Electrical Underground
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2026 | COT - LCEL - Electrical Underground | Partial Pass | Conduit line 3/4” at West side of site; approximately 100’ of trench. Ok to cover progress area. | |
| 01/07/2026 | COT - LCEL - Electrical Underground | Partial Pass | Underground conduit from first light pole near 6th av ran along the side walk south west of park at a 22” depth. Tied into a total of 4 light poles. End of run is at the 5th light pole. At LP1004A. North side of park at side walk underground conduit from end of run near building light pole to 3rd light pole. Okay to backfill all progress areas. Shading required. 1/7/2026 | |
| 01/16/2026 | COT - LCEL - Electrical Underground | Partial Pass | Two historical light pole bases approved. Okay for concrete placement. (Near the building. 30” diameters) 1/15/2026 | |
| 11/10/2025 | COT - LCEL - Electrical Underground | Partial Pass | North side: dog park: 1” conduit for 7 light poles. Ok to.cover progress areas. | |
| 11/20/2025 | COT - LCEL - Electrical Underground | Partial Pass | Electric conduit lines at 3/4” from building area to pavilion. |