Parcel: 12408190C

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Final 

Permit Number - TC-COM-0525-00936

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/15/2026 COT - LCEL - Electrical Final  Partial Pass Room units #103 and #203 are complete.
03/02/2026 COT - LCEL - Electrical Final  Not Ready
03/12/2026 COT - LCEL - Electrical Final  Re-inspection required Kitchen circuits, IEGFI dishwasher and garbage disposal are not wired per plant panel schedule is not completed. Microwave does not have the space required under the microwave to the stove top. Inspection stopped]]

3/11/26: Units (104,105,106,107,204,205,206,207) were walked for final inspections, GFCI and AFCI receptacles required throughout please ensure all NEC requirements are met, anti-tip at range required, water heater cannot be energized with flexible cord, insulation required at hot water heater hot side, air handler shall be fed with 15 amp breaker, verify electrical air handler can be installed with flexible cord per manufacturer requirements. Roofs must be walked at finals, ensure all kitchen exhaust dampers are properly functioning, properly terminate water heater drain.
03/16/2026 COT - LCEL - Electrical Final  Partial Pass 3/16/2026 all corrections were made. (104,105,106,107,204,205,206,207) all units have been approved.
12/29/2025 COT - LCEL - Electrical Final  Partial Pass Units 101, 102, 201, 202. Complete.