Inspection Status: Re-inspection required

Inspection History: COT - LCME - Mechanical Intermediate

Date Description Inspector Results Comments
06/20/2025 COT - LCME - Mechanical Intermediate Re-inspection required Fuses for unit 2 are oversized, should be 40amps, is 45, fuses for unit 1 undersized, should be 50 amps. All exterior pvc should be painted, condensation lines not supported by blocks, blocks not attached to roof
06/27/2025 COT - LCME - Mechanical Intermediate Passed 6/27/25 corrections made