Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2025 |
COT - LCME - Mechanical Final |
|
Re-inspection required |
Fuses for unit 2 are oversized, should be 40amps, is 45, fuses for unit 1 undersized, should be 50 amps. All exterior pvc should be painted, condensation lines not supported by blocks, blocks not attached to roof |
| 06/27/2025 |
COT - LCME - Mechanical Final |
|
Passed |
6/27/25 corrections made |