Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Framing
Permit Number - TC-COM-0524-00990
Inspection Description - COT - LCBU - Framing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2024 | COT - LCBU - Framing | Re-inspection required | 1-Corner stud has been scabbed with approximately 4" overlap to block nailed to actual corner stud; this allows a bow present at time of inspection. 2-Sheathing is damaged approximately 6" from corner thus contributing to bow. 3-Multiple sole plates are split and missing nuts/washers. 4-Interior corner stud is bowing inward. 5-Multiple studs are not connected to sole plates adequately. | |
08/09/2024 | COT - LCBU - Framing | Passed |