Inspection History: BULD - Electrical Clearance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2024 | BULD - Electrical Clearance | Re-inspection required | Fail - 2 meters and disconnects are served through a gutter system and both shall be approved together (recommend service panel upgrades) 1. please add 2 ground rods and #4 grounding conductor, also gas and water bonds are required. 2. Missing smoke detectors in both units 3. Verify sub-panel compliance |
|
| 05/24/2024 | BULD - Electrical Clearance | Passed | Corrections were made. Clearance for TEP RECN for BOTH UNITS. 5/24/2024 |