Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 08/26/2024 |
COT - LCEL - Electrical Final |
|
Not Ready |
|
| 08/29/2024 |
COT - LCEL - Electrical Final |
|
Partial Pass |
Canceled by contractor smoke detectors not interconnected |
| 09/05/2024 |
COT - LCEL - Electrical Final |
|
Passed |
|