Parcel: 13219102B


Addresses:

4733 S CAMPBELL AV


Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Permit Number - TC-COM-0523-01312

Inspection Description - COT - HCEL - Electrical Underground 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/26/2024 COT - HCEL - Electrical Underground  Partial Pass 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
01/31/2024 COT - HCEL - Electrical Underground  Partial Pass 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
1/31/24: electrical underground at tank section per plan ok to backfill.
02/06/2024 COT - HCEL - Electrical Underground  Partial Pass 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
1/31/24: electrical underground at tank section per plan ok to backfill.
2/6/24: underground electrical from Kiosk to transformer 70ft stretch ok to back fill.
02/08/2024 COT - HCEL - Electrical Underground  Partial Pass
02/12/2024 COT - HCEL - Electrical Underground  Partial Pass
02/15/2024 COT - HCEL - Electrical Underground  Partial Pass 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
1/31/24: electrical underground at tank section per plan ok to backfill.
2/6/24: underground electrical from Kiosk to transformer 70ft stretch ok to back fill.
2/8/24 from mid span of canopy on the north side to mid span of canopy of the east side 3 2.5" secondary lines ok to cover
2/12/24 ok to cover 3 conduits from main building to kiosk
2/15/24: stub-outs at kiosk complete ok to backfill.
02/21/2024 COT - HCEL - Electrical Underground  Partial Pass 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
1/31/24: electrical underground at tank section per plan ok to backfill.
2/6/24: underground electrical from Kiosk to transformer 70ft stretch ok to back fill.
2/8/24 from mid span of canopy on the north side to mid span of canopy of the east side 3 2.5" secondary lines ok to cover
2/12/24 ok to cover 3 conduits from main building to kiosk
2/15/24: stub-outs at kiosk complete ok to backfill.
2/21/24: stub-outs at kiosk complete ok to backfill.
02/27/2024 COT - HCEL - Electrical Underground  Partial Pass
03/08/2024 COT - HCEL - Electrical Underground  Passed 1/26/24: electrical underground for fuel dispenser and lighting per plan ok to back fill completed areas. Shading required. Pending point of connection to kiosk on north east of canopy.
1/31/24: electrical underground at tank section per plan ok to backfill.
2/6/24: underground electrical from Kiosk to transformer 70ft stretch ok to back fill.
2/8/24 from mid span of canopy on the north side to mid span of canopy of the east side 3 2.5" secondary lines ok to cover
2/12/24 ok to cover 3 conduits from main building to kiosk
2/15/24: stub-outs at kiosk complete ok to backfill.
2/21/24: stub-outs at kiosk complete ok to backfill.
2/27/24 primary and secondary's are complete ok to cover and underground electric to two light pole bases OK to cover
3/8/24: electrical underground complete. Grounding per plan. Passed