Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - CSOL - Electrical Underground Solar Project
Permit Number - TC-COM-0425-00669
Inspection Description - COT - CSOL - Electrical Underground Solar Project
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2025 | COT - CSOL - Electrical Underground Solar Project | Partial Pass | Partial pass. From new transformer pad to new DG equipment. From DG equipment to point of connection . X3 3 1/2" conduit schedule 40 at 24"depth. 1" conduit for grounding electrode. Okay to backfill progress areas. Shading required. 12/22/2025 |