Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - LCME - Mechanical Intermediate
Permit Number - TC-COM-0424-00685
Inspection Description - COT - LCME - Mechanical Intermediate
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2026 | COT - LCME - Mechanical Intermediate | Partial Pass | 1-9-26: mechanical & electrical above ceiling at coating room 1 & breezeway in Area C approved. Okay to install tiles & hard grid. | |
| 01/21/2026 | COT - LCME - Mechanical Intermediate | Canceled | 1-21-26: canceled by contractor. | |
| 01/26/2026 | COT - LCME - Mechanical Intermediate | Partial Pass | 1-26-26: partial pass-worker on site working on supports. | |
| 02/05/2026 | COT - LCME - Mechanical Intermediate | Partial Pass | 2-5-26: okay to cover progress areas at ceiling. Install registers and will verify above ceiling at finals. | |
| 02/25/2026 | COT - LCME - Mechanical Intermediate | Passed | 2-25-26: approved. | |
| 12/17/2025 | COT - LCME - Mechanical Intermediate | Re-inspection required | 12-17-25: copper air line, fire sprinkler, together with condensation copper line above ceiling cannot be in contact with other metals-add 10 mil tape or install copper hangers, add insulation around pookie joints, replace/add duct hanger on south end of shipping/receiving/control area. | |
| 12/22/2025 | COT - LCME - Mechanical Intermediate | Partial Pass | 12-22-25: partial pass-okay to continue with construction at quality control & shipping/receiving areas. |