Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Intermediate
Permit Number - TC-COM-0424-00685
Inspection Description - COT - LCME - Mechanical Intermediate
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2025 | COT - LCME - Mechanical Intermediate | Re-inspection required | 12-17-25: copper air line, fire sprinkler, together with condensation copper line above ceiling cannot be in contact with other metals-add 10 mil tape or install copper hangers, add insulation around pookie joints, replace/add duct hanger on south end of shipping/receiving/control area. |