Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - LCME - Mechanical Intermediate

Permit Number - TC-COM-0424-00685

Inspection Description - COT - LCME - Mechanical Intermediate

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
12/17/2025 COT - LCME - Mechanical Intermediate Re-inspection required 12-17-25: copper air line, fire sprinkler, together with condensation copper line above ceiling cannot be in contact with other metals-add 10 mil tape or install copper hangers, add insulation around pookie joints, replace/add duct hanger on south end of shipping/receiving/control area.