Inspection Status: Canceled
Inspection History: COT - LCPL - Plumbing Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2026 |
COT - LCPL - Plumbing Intermediate |
|
Canceled |
1-21-26: canceled by contractor. |
| 01/26/2026 |
COT - LCPL - Plumbing Intermediate |
|
Re-inspection required |
1-26-26: label all junction boxes above ceiling, hot copper water lines 3/4" or larger must be insulation with minimum of R3, add 10 mil tape to all locations where copper lines are in contact with seismic wires, provide supports to copper lines that are resting directly on top of ceiling grid (supports attached directly to the ceiling grid is not allowed). Reschedule inspection when corrections are made. |
| 02/05/2026 |
COT - LCPL - Plumbing Intermediate |
|
Partial Pass |
2-5-26: corrections made-okay to cover progress areas at ceiling. |
| 02/25/2026 |
COT - LCPL - Plumbing Intermediate |
|
Passed |
2-25-26: approved. |
| 05/29/2025 |
COT - LCPL - Plumbing Intermediate |
|
Not Ready |
|
| 09/17/2025 |
COT - LCPL - Plumbing Intermediate |
|
Partial Pass |
9-17-25: new underground plumbing for a new shower & water station located at Area B approved-Okay to backfill progress areas. |