Inspection Status: Canceled
Inspection History: COT - HCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 03/07/2025 |
COT - HCEL - Electrical Underground |
|
Canceled |
3-7-25, canceled by contractor. |
| 03/10/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
Conduits at North exterior wall. |
| 03/11/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
Under building. |
| 03/21/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
30' North of service store. |
| 03/24/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
3-24-25, 60' of 1 inch conduits for dispenser and approximately 70' of 1 inch conduits for tents verified per plans. Okay to backfill trenches. |
| 04/03/2025 |
COT - HCEL - Electrical Underground |
|
Not Ready |
Software mishap. |
| 04/09/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
under canopy |
| 04/17/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
4-17-25, okay to backfill approximately 100' of 3" secondary electrical conduits on south side of building. Rough-in mechanical verified per plans-okay to continue with construction at progress areas. |
| 04/25/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
Light pole bases. |
| 04/30/2025 |
COT - HCEL - Electrical Underground |
|
Passed |
|