Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Permit Number - TC-COM-0423-01023

Inspection Description - COT - LCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
02/13/2024 COT - LCBU - Building Final  Re-inspection required Water and DWV.
2/13/24: Restroom Not ADA compliant, GFCI at restroom not functioning properly, Air Gap required at sinks in kitchen, UV coat all exterior piping, Panel schedule not complete, pending water sterilization report, health inspection. TMV missing at bathroom lav, water hammer arrestor missing at water closet. More items may be added.
02/26/2024 COT - LCBU - Building Final  Passed ok for C/O