Parcel: 13216600A


Addresses:

4410 S PARK AV


Inspection Status: Partial Pass

Inspection History: COT - LCEL - Grounding/Bonding 

Permit Number - TC-COM-0423-00942

Inspection Description - COT - LCEL - Grounding/Bonding 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
10/09/2024 COT - LCEL - Grounding/Bonding  Partial Pass 10/9/24: partial for UFER
11/15/2024 COT - LCEL - Grounding/Bonding  Partial Pass 10/9/24: partial for UFER
Partial pass. Electrical. Stubbed up vertically. D area. Out door receptacles. Controls for garage door. 10/18/2024

10/23/24: electrical underground at MDF room 114 passed, (8)4” conduit 50’ run from building at SES to transformer, electrical underground for ATS per plans, electrical underground at room 196 per plans ok to proceed.
11/14/24: electrical underground passed from room 226 (COMM) to room 114 (MDF), storage room to ATS complete ok to backfill.

11/15/24: reinforcement/ grounding per plan at 3 light pole base SG at north west trash enclosure.