Inspection Status: Partial Pass
Inspection History: COT - LCME - Mechanical Progress
Permit Number - TC-COM-0423-00942
Inspection Description - COT - LCME - Mechanical Progress
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2025 | COT - LCME - Mechanical Progress | Partial Pass | 5/30/25: Okay to insulate supply duct in progress areas in locker room, fitness room to Tactics room, main supply duct from fitness room from RTU-2 down corridor 149 to room 163, Room 148. | |
| 06/03/2025 | COT - LCME - Mechanical Progress | Partial Pass | Two sets of refrigerant lines in room 226 for mini splits approved. 6/3/2025 | |
| 06/10/2025 | COT - LCME - Mechanical Progress | Partial Pass | Three sets of Refrigent lines in MDF 114 room for mini splits approved. 6/10/2025 | |
| 06/20/2025 | COT - LCME - Mechanical Progress | Partial Pass | Supply air duct systems in Restrooms #105, Tactics room, MDF Room #114, Fitness room, men’s and women’s locker rooms, break (eating) room #148, briefing room #163. Ok to insulate inspected duct systems. | |
| 07/22/2025 | COT - LCME - Mechanical Progress | Partial Pass | Duct works systems in Areas C and D except for 5 VAB units in Northeast portion of Area C. | |
| 07/25/2025 | COT - LCME - Mechanical Progress | Partial Pass | 5/30/25: Okay to insulate supply duct in progress areas in locker room, fitness room to Tactics room, main supply duct from fitness room from RTU-2 down corridor 149 to room 163, Room 148. Two sets of refrigerant lines in room 226 for mini splits approved. 6/3/2025 Three sets of Refrigent lines in MDF 114 room for mini splits approved. 6/10/2025 7/25/24: VAV installed in room 111,123,124,113,121 Area C |
|
| 08/26/2025 | COT - LCME - Mechanical Progress | Partial Pass | Metal duct systems in processing area; ensure pooky covering is complete on all ducts. | |
| 11/03/2025 | COT - LCME - Mechanical Progress | Partial Pass | 11-3-25: 2nd wrap of grease ducts for kitchen hoods in room's 148 & 204 approved. Okay to continue with construction at progress areas. | |
| 11/13/2025 | COT - LCME - Mechanical Progress | Partial Pass | 11-13-25: mechanical, electrical and plumbing above ceiling at Debriefing and interview lobby LMS approved. Okay to continue with construction at progress areas. |