Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2026 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
Partial pass. South soccer field. From 2nd musco lighting pole south west corner. Approximately 70’ of X1 1 1/2” schedule 40 at 24” depth. Up to double box ran along all west end of soccer field to double box at south west corner. Approximately 235’. From double box ran north of soccer field to musco light pole approximately 70’. Olay to backfill all progress areas. Shading required. Ensure caution tape is in place after first lift of compaction. 8/5/2026 |