Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2026 |
COT - LCEL - Electrical Above Ceiling |
|
Re-inspection required |
4-21-26: inspection for above ceiling lights at Porte Cochere. The approved plans call for 12 can lights, however, only 9 were installed. Please submit an RFI be submitted to the city for review/approval showing the made change. Okay to cover above ceiling using gyp board at own risk. Also, schedule a drywall screw inspection prior to tape & texture. |