Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Final
Permit Number - TC-COM-0325-00441
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2025 | COT - LCEL - Electrical Final | Re-inspection required | Not ready. Plans call for three new wall mounted fan coil units. In field two have been installed. Mini split on plan calls for Daikin models. Gree models have been installed throughout. Provide proper listing to state they are in accordance with UL 1995 or UL/CSA/ANCE 60335-2-40. Per code M1403.1. Label on the current model do not state the min or max size breaker. Coat all exterior condensation pipes for UV protection. 4/16/2025 | |
| 08/18/2025 | COT - LCEL - Electrical Final | Passed | Approved. All corrections have been made. Plans have been revised to what's installed in field. 8/18/2025 |