Parcel: 12315233A

Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Permit Number - TC-COM-0325-00441

Inspection Description - COT - LCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/16/2025 COT - LCBU - Building Final  Re-inspection required Not ready. Plans call for three new wall mounted fan coil units. In field two have been installed. Mini split on plan calls for Daikin models. Gree models have been installed throughout. Provide proper listing to state they are in accordance with UL 1995 or UL/CSA/ANCE 60335-2-40. Per code M1403.1. Label on the current model do not state the min or max size breaker. Coat all exterior condensation pipes for UV protection. 4/16/2025
08/18/2025 COT - LCBU - Building Final  Passed Approved. All corrections have been made. Plans have been revised to what's installed in field. 8/18/2025