Inspection Status: Re-inspection required

Inspection History: COT - FCON - Sprinkler - Final

Permit Number - TC-COM-0324-00526

Inspection Description - COT - FCON - Sprinkler - Final

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/29/2024 COT - FCON - Sprinkler - Final Re-inspection required Sprinkler head in lobby that is to close to the wall needs to be moved , a sprinkler head needs to be added in the corner of the lobby that is obstructed, back office ceiling not intact, trim rings missing in back room, several sprinkler heads have been painted.
07/02/2024 COT - FCON - Sprinkler - Final Passed