Inspection Status: Re-inspection required
Inspection History: COT - LCPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2025 |
COT - LCPL - Plumbing Final |
|
Re-inspection required |
4/22/25: ADA requirements not met, Water heater Pressure relief valve must terminate to exterior, water heater not installed per plans, HVAC condensate not installed, all exterior plastic piping must be coated for UV protection, Clean outs missing per caps must be listed for use, lav drain not code complaint, GFCI receptacles required at utility room, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 04/24/2025 |
COT - LCPL - Plumbing Final |
|
Passed |
|