Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Permit Number - TC-COM-0324-00516

Inspection Description - COT - LCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/22/2025 COT - LCBU - Building Final  Re-inspection required 4/22/25: ADA requirements not met, Water heater Pressure relief valve must terminate to exterior, water heater not installed per plans, HVAC condensate not installed, all exterior plastic piping must be coated for UV protection, Clean outs missing per caps must be listed for use, lav drain not code complaint, GFCI receptacles required at utility room, STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
04/24/2025 COT - LCBU - Building Final  Deferred 4/22/25: ADA requirements not met, Water heater Pressure relief valve must terminate to exterior, water heater not installed per plans, HVAC condensate not installed, all exterior plastic piping must be coated for UV protection, Clean outs missing per caps must be listed for use, lav drain not code complaint, GFCI receptacles required at utility room, STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
4/24/25: passed, pending conditions
04/24/2025 COT - LCBU - Building Final  Re-inspection required