Inspection Status: Partial Pass

Inspection History: COT - HCBU - Exterior Clips/Sheathing 

Permit Number - TC-COM-0323-00830

Inspection Description - COT - HCBU - Exterior Clips/Sheathing 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/05/2024 COT - HCBU - Exterior Clips/Sheathing  Partial Pass 1/5/24: Exterior clips per plan ok to start sheathing. Will verify S/hdu4 holdowns at sheathing inspection. RFI will be needed for substitution in holdowns.
01/16/2024 COT - HCBU - Exterior Clips/Sheathing  Partial Pass 1/5/24: Exterior clips per plan ok to start sheathing. Will verify S/hdu4 holdowns at sheathing inspection. RFI will be needed for substitution in holdowns.
1/16/24: S/hdu4 holdowns verified. Pending exterior sheathing inspection and anchor bolt inspection at interior and exterior walls.
02/13/2024 COT - HCBU - Exterior Clips/Sheathing  Re-inspection required 1/5/24: Exterior clips per plan ok to start sheathing. Will verify S/hdu4 holdowns at sheathing inspection. RFI will be needed for substitution in holdowns.
1/16/24: S/hdu4 holdowns verified. Pending exterior sheathing inspection and anchor bolt inspection at interior and exterior walls.
2/13/24: Anchor bolt spacing is greater than 48" O.C throughout building (missing throughout), stud spacing is 16" O.C per plan (installed at 24" O.C)
02/26/2024 COT - HCBU - Exterior Clips/Sheathing  Passed 1/5/24: Exterior clips per plan ok to start sheathing. Will verify S/hdu4 holdowns at sheathing inspection. RFI will be needed for substitution in holdowns.
1/16/24: S/hdu4 holdowns verified. Pending exterior sheathing inspection and anchor bolt inspection at interior and exterior walls.
2/13/24: Anchor bolt spacing is greater than 48" O.C throughout building (missing throughout), stud spacing is 16" O.C per plan (installed at 24" O.C)
2/26/24: RFI for studs spacing at 24" O.C approved. Anchor bolts installed at exterior walls throughout. Corrections made passed.