Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Permit Number - TC-COM-0323-00758

Inspection Description - COT - HCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
02/14/2024 COT - HCBU - Building Final  Re-inspection required 2/14/24: Receptacles on exterior of building missing bubble cover, receptacles on exterior require WR receptacles, missing GFCI receptacles within 6' of water source, properly support electrical whips on roofs for coolers, A/C units are being over Amped, UV coat all insulation on refrigerant lines, condensation line in walk in freezer not properly draining, condensate line at walk in freezer must be insulated, pending air balance/ hood duct performance test.
02/15/2024 COT - HCBU - Building Final  Passed 2/14/24: Receptacles on exterior of building missing bubble cover, receptacles on exterior require WR receptacles, missing GFCI receptacles within 6' of water source, properly support electrical whips on roofs for coolers, A/C units are being over Amped, UV coat all insulation on refrigerant lines, condensation line in walk in freezer not properly draining, condensate line at walk in freezer must be insulated, pending air balance/ hood duct performance test.
2/15/24: corrections made.