Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Gas Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2024 | COT - HCPL - Gas Final | Re-inspection required | 2/14/24: Receptacles on exterior of building missing bubble cover, receptacles on exterior require WR receptacles, missing GFCI receptacles within 6' of water source, properly support electrical whips on roofs for coolers, A/C units are being over Amped, UV coat all insulation on refrigerant lines, condensation line in walk in freezer not properly draining, condensate line at walk in freezer must be insulated, pending air balance/ hood duct performance test. | |
| 02/15/2024 | COT - HCPL - Gas Final | Passed | 2/14/24: Receptacles on exterior of building missing bubble cover, receptacles on exterior require WR receptacles, missing GFCI receptacles within 6' of water source, properly support electrical whips on roofs for coolers, A/C units are being over Amped, UV coat all insulation on refrigerant lines, condensation line in walk in freezer not properly draining, condensate line at walk in freezer must be insulated, pending air balance/ hood duct performance test. 2/15/24: corrections made. |