Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
09/10/2026 BULD - Electrical Clearance Re-inspection required 9/10/26: 169( GFCI required at kitchen kitchen receptacle spacing at counter can’t be more than 24” from edge,replace sub panel( has been painted), exterior receptacle must have weather cover and be GFCI,

170(properly secure electrical whip 12” from box, label and replace cover at sub panel),

168 (GFCI required in bathroom, panel must be replaced, anti tip required at range,

167( secure flexible whip 12” from receptacle)

166 ( secure flexible whip 12” from receptacle)

165(( secure flexible whip 12” from receptacle)

164 ( secure flexible whip 12” from receptacle)

163
09/13/2026 BULD - Electrical Clearance Not Applicable