Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Date Description Inspector Results Comments
09/10/2026 COT - LCBU - Building Final  Re-inspection required 9/10/26: 169( GFCI required at kitchen kitchen receptacle spacing at counter can’t be more than 24” from edge,replace sub panel( has been painted), exterior receptacle must have weather cover and be GFCI,

170(properly secure electrical whip 12” from box, label and replace cover at sub panel),

168 (GFCI required in bathroom, panel must be replaced, anti tip required at range,

167( secure flexible whip 12” from receptacle)

166 ( secure flexible whip 12” from receptacle)

165(( secure flexible whip 12” from receptacle)

164 ( secure flexible whip 12” from receptacle)

163
09/13/2026 COT - LCBU - Building Final  Re-inspection required 163

9/11/26:
261 bathroom GFCI sticker, 262 GFCI sticker at bathroom and pain on sub panel, 263 gfci at kitchen area no power, 264 gfci sticker at bathroom, 265 all good, 266 all good, 267 all good, 268 all good, 269 all good, 270 all good, 271 sticker GFCI
09/16/2026 COT - LCBU - Building Final  Partial Pass 9/16/2026 Partial pass. Building 3. Units 261,262,263,264,271,163,164,165,166,167,Approved. All corrections were made.