Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building FinalĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2026 |
COT - HCBU - Building FinalĀ |
|
Re-inspection required |
10/27/26: have architect submit a complete electrical plan to the city for review/approval, label junction boxes above ceiling, install 240 volt outlet at south wall of warehouse. Complete landscape, provide a fix for downspout over walkway on east side (cannot drain on sidewalk creating a trip hazard), label subpanel, schedule all remaining inspections and upload all 3rd party reports for review. |