Inspection Status: Not Ready

Inspection History: COT - HCBU - Interior Shear Bracing 

Permit Number - TC-COM-0225-00242

Inspection Description - COT - HCBU - Interior Shear Bracing 

Inspection Status - Not Ready

Date Description Inspector Results Comments
07/25/2025 COT - HCBU - Interior Shear Bracing  Not Ready 7-25-25: not ready.
08/05/2025 COT - HCBU - Interior Shear Bracing  Re-inspection required 8-5-25: missing drywall at south farm table, north wall at dining room wall missing screws along joints/edges, screws must be installed no closer than 3/8" from edges/joints and shall not over penetrate more than 1/32"-check spacing along edges at cook line, office, hallway, and add screws according to schedule throughout. Reschedule inspection but okay to tape & texture restrooms.
08/06/2025 COT - HCBU - Interior Shear Bracing  Passed