Parcel: 112070180

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Underground 

Permit Number - TC-COM-0224-00349

Inspection Description - COT - LCEL - Electrical Underground 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
08/18/2025 COT - LCEL - Electrical Underground  Partial Pass
08/20/2025 COT - LCEL - Electrical Underground  Partial Pass
09/26/2025 COT - LCEL - Electrical Underground  Partial Pass 3” for well pump from pump control panel to well head.
Air compressor and chlorine building (co2) x2 3/4” and 1” from electrical rack to chlorine building.
X3 3/4” and X3 1” from electrical rack to level sensor and pressure pedestal. All schedule 40 at 32” depth. Okay to backfill all progress areas. Shading required. 9/26/2025