Inspection Status: Not Ready
Inspection History: COT - LCBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2024 |
COT - LCBU - Building Final |
|
Not Ready |
|
| 05/19/2025 |
COT - LCBU - Building Final |
|
Re-inspection required |
5-19-25, handrail height shall be 36" max, flush control device shall be on accessible side, soap & hand towel dispenser height shall be 46" aff, missing men's/woman sign with braille, all other bathrooms not ADA compliant, restroom fixtures do not match with what's indicated & approved on plans. Missing water heater under sink cabinet in activity room #4, STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED. |
| 05/19/2025 |
COT - LCBU - Building Final |
|
Re-inspection required |
5-19-25, see previous notes reference engineering & fire inspection. Also, have set of proved plans on site and intermediate inspections have not been approved. |
| 06/17/2025 |
COT - LCBU - Building Final |
|
Re-inspection required |
6-17-25: install vacuum breaker at hose bib, replace water closet and reschedule finals and intermediates. |
| 06/18/2025 |
COT - LCBU - Building Final |
|
Partial Pass |
6-18-25: pending water sterilization report. Submit report to the city as an attachment for review and approval. Remove all concrete debris next to trash enclosure. |
| 06/26/2025 |
COT - LCBU - Building Final |
|
Passed |
|