Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
3-13-25, electrical conduits for kitchen and BMS (lighting ) panels verified per plans. Okay to backfill at progress areas. |
| 04/02/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
4-2-25, okay to backfill approximately 60 ft. Of 4inch Schedule 40 conduits leading up to transformer. |
| 06/05/2025 |
COT - HCEL - Electrical Underground |
|
Partial Pass |
6-5-25: verified trench depth for 6-1" Schedule 40 electrical conduits located on west side. Okay to backfill approximately 130' of open trench. |
| 08/08/2025 |
COT - HCEL - Electrical Underground |
|
Passed |
8-8-25: approved |