Permit: TC-COM-0224-00312

Parcel: 12412006A


Addresses:

1046 E BROADWAY BL

Inspection Status: Partial Pass

Inspection History: COT - LCPL - Plumbing Final 

Date Description Inspector Results Comments
02/24/2026 COT - LCPL - Plumbing Final  Partial Pass Partial pass. Insulate hot lines coming from water heater. Provide chlorination report. 2/24/2026
03/12/2026 COT - LCPL - Plumbing Final  Re-inspection required 3/12/26: ensure all j-boxes and open knock outs at j-boxes are sealed, drinking fountain shall be no higher than 36" above finish floor to spout outlet, grab bars in restroom do not meet A117.1 requirements (36" bar required behind water closet, location of vertical grab bar), bathroom lav above the max 34" above finish floor, mirror shall not be higher than 40" to reflective surface, water heater must be insulated. Signage for restrooms required
03/25/2026 COT - LCPL - Plumbing Final  Passed 3/25/2026 all corrections were made.