Inspection Status: Not Ready
Inspection History: ENGR Engineering Final
Permit Number - TC-COM-0224-00312
Inspection Description - ENGR Engineering Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2026 | ENGR Engineering Final | Not Ready | Site is not finished. No striping, no handicap or standard parking spaces and no wheel stops. Current access ramp does not comply. The ROW sidewalk is being built now and it is an active construction site. | |
| 03/12/2026 | ENGR Engineering Final | Re-inspection required | Landing at entrance door needs to be 60" x 60". Ramp into building is 20% slope, maximum allowed without handrails is 5%. No ADA parking sign, need sign indicating van accessible handicapped parking. Landscape incomplete, missing plants. |