Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Final
Permit Number - TC-COM-0224-00312
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2026 | COT - LCEL - Electrical Final | Not Ready | ||
| 03/12/2026 | COT - LCEL - Electrical Final | Re-inspection required | 3/12/26: ensure all j-boxes and open knock outs at j-boxes are sealed, drinking fountain shall be no higher than 36" above finish floor to spout outlet, grab bars in restroom do not meet A117.1 requirements (36" bar required behind water closet, location of vertical grab bar), bathroom lav above the max 34" above finish floor, mirror shall not be higher than 40" to reflective surface, water heater must be insulated. |