Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: COT - HCPL - Plumbing Final
Permit Number - TC-COM-0224-00272
Inspection Description - COT - HCPL - Plumbing Final
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2026 | COT - HCPL - Plumbing Final | Passed | 1/6/2026 all corrections have been made. | |
| 12/16/2025 | COT - HCPL - Plumbing Final | Re-inspection required | 12/16/25: rooms 4107,4105,4106,4108,4208,4206,4205,4207 were inspected ( insulation required at hot water lines at utility room, water hammer arrestor required on washer box, 4107 strobing lights not properly functioning, window fall protection might be required per IBC 1015.8, water heater electrical whip must be connected to water heater 4205) | |
| 12/18/2025 | COT - HCPL - Plumbing Final | Re-inspection required | 12-18-25: 4204-missing hammer arrestors at dishwasher/washer box, insulation missing at hot water line at utility room, no running water at kitchen sink, firefoam penetrations at utility room. 4202-insulation missing on hot water lines at utility room, fire foam penetrations, hammer arrestor required at laundry, check water pressure at kitchen sink. 4203-Seal penetration at utility room, insulation missing on hot water line at utility room, check water pressure at kitchen sink.4201-insulation on hot water lines missing at utility, seal penetration in utility, check water pressure at kitchen sink. Per previous notes-fall protection may be required. |