Inspection History: COT - HCME - Mechanical Final
Permit Number - TC-COM-0224-00272
Inspection Description - COT - HCME - Mechanical Final
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2026 | COT - HCME - Mechanical Final | Passed | 1/6/2026 all corrections have been made. | |
| 12/16/2025 | COT - HCME - Mechanical Final | Re-inspection required | 12/16/25: rooms 4107,4105,4106,4108,4208,4206,4205,4207 were inspected ( insulation required at hot water lines at utility room, water hammer arrestor required on washer box, 4107 strobing lights not properly functioning, window fall protection might be required per IBC 1015.8, water heater electrical whip must be connected to water heater 4205) | |
| 12/18/2025 | COT - HCME - Mechanical Final | Re-inspection required | 12-18-25: 4204-missing hammer arrestors at dishwasher/washer box, insulation missing at hot water line at utility room, no running water at kitchen sink, firefoam penetrations at utility room. 4202-insulation missing on hot water lines at utility room, fire foam penetrations, hammer arrestor required at laundry, check water pressure at kitchen sink. 4203-Seal penetration at utility room, insulation missing on hot water line at utility room, check water pressure at kitchen sink.4201-insulation on hot water lines missing at utility, seal penetration in utility, check water pressure at kitchen sink. Per previous notes-fall protection may be required. |