Inspection History Details
Inspection Status: Re-inspection required
Inspection History: Pool/Spa - Final/Barrier
Permit Number - TC-COM-0223-00696
Inspection Description - Pool/Spa - Final/Barrier
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2025 | Pool/Spa - Final/Barrier | Re-inspection required | site under new ownership and no longer per approved plans, needs revision | |
| 06/27/2025 | Pool/Spa - Final/Barrier | Re-inspection required | 6/27/25: revision required regarding site location of pool. hand rails and step ladders not set in place at time of final inspection. exterior GFCI receptacles missing at exterior throughout,Emergency disconnect required at equipment room, B-vent for heaters require proper clearance from combustibles, all equipment must be properly secured to foundation, will need access into office/mail room to ensure all doors/openings meet requirements. | |
| 08/07/2025 | Pool/Spa - Final/Barrier | Passed |