Inspection Status: Requested

Inspection History: COT - HCME - Mechanical Above Ceiling

Permit Number - TC-COM-0125-00202

Inspection Description - COT - HCME - Mechanical Above Ceiling

Inspection Status - Requested

Date Description Inspector Results Comments
COT - HCME - Mechanical Above Ceiling Requested
01/07/2026 COT - HCME - Mechanical Above Ceiling Re-inspection required 1-7-26: 415-missing pookie and exhaust strap, 416-missing pookie at exhaust, 418-pookie seal at north wall, 426-pookie at exhaust, 430-pookie at marked location, 434-pookie at marked location.
01/12/2026 COT - HCME - Mechanical Above Ceiling Re-inspection required (with fee) 1-12-26: room's 201-220 inspected. 201-add Boca plates to exhaust at party wall, Add pookie above ceiling, 209-make corrections or replace restroom exhaust, pookie and Boca plates to exhaust at party wall, 211-pookie, 213-pookie, 215-pookie, 217-pookie, 220-pookie at exhaust
12/23/2025 COT - HCME - Mechanical Above Ceiling Re-inspection required 12/23/25: Exhaust ducts must be properly sealed and supported throughout on third floor, Boca plates required throughout at Exhaust duct, 4th floor was not walked (ceilings have been covered prior to inspection) please recall once access is available for above ceiling inspection.