Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Above Ceiling
Permit Number - TC-COM-0125-00202
Inspection Description - COT - HCEL - Electrical Above Ceiling
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2026 | COT - HCEL - Electrical Above Ceiling | Re-inspection required | 1-5-26: 3rd floor rough electrical-328- add bank plate at party wall where awg wires are 1 1/4" from edge, 334-fire foam penetrations at decking in restroom, 325-add bank plate center near subpanel at marked location, 323-fire foam top plate penetration backside of tub. Fire foam all penetrations at party walls and at decking throughout all rooms. These items will be re-inspected at intermediates. Note: framing inspection on any floor has not taken place and see previous notes related to 4th floor above ceiling-several rooms had already been covered with cloth material and this must be removed and a reinspection is required. |
|
| 12/09/2025 | COT - HCEL - Electrical Above Ceiling | Partial Pass | Partial pass. 4th floor approved. Pending fire blocking at all top plates and near all tubs. 12/9/2025 | |
| 12/10/2025 | COT - HCEL - Electrical Above Ceiling | Not Ready | 12/10/25: not ready for inwall inspection or above ceiling. | |
| 12/22/2025 | COT - HCEL - Electrical Above Ceiling | Re-inspection required | 12-22-25: rough electrical in wall /above ceiling-fire foam horizontal penetrations at party wall, add bank plates where closer than 1 1/4" from edges, finish rough in electrical from unit's 321/322 to north-awg wires must be made up at time of inspection. |