Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Above Ceiling 

Date Description Inspector Results Comments
01/05/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 1-5-26: 3rd floor rough electrical-328- add bank plate at party wall where awg wires are 1 1/4" from edge, 334-fire foam penetrations at decking in restroom, 325-add bank plate center near subpanel at marked location, 323-fire foam top plate penetration backside of tub. Fire foam all penetrations at party walls and at decking throughout all rooms. These items will be re-inspected at intermediates.
Note: framing inspection on any floor has not taken place and see previous notes related to 4th floor above ceiling-several rooms had already been covered with cloth material and this must be removed and a reinspection is required.
01/20/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass Electric above ceilings and in walls in room units on Level,#4.
01/22/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass Level #2, room units; Electric in walls and above ceilings.
02/12/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 2-12-26: electrical corrections made for units 101-111 & 102-112. Okay to continue with construction.
02/19/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 2-19-26: reschedule inspection when ready.
02/23/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass Room units at North portion of Level #1 from elevator area to North end. Ok to sheet rock ceiling areas.
03/31/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 3-31-26: inspection for 1st hard lid areas in corridor and electrical room. Fire foam all penetrations at top plates, all horizontal penetrations and at decking. Add a strap to DWV at electrical room north wall
04/28/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 4-28-26: electrical above ceiling at canopy approved. Okay to continue with construction at progress areas.
04/30/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 4-30-26: 1st. floor not ready- non sealed penetrations throughout including low voltage, open junction boxes and not labeled, sections of missing drywall, 1" hot pex lines not insulated. 3rd floor-Open penetrations at south end of corridor and a couple of junction boxes not labeled. 4th floor electrical above ceiling approved.
05/04/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 5/4/2026 corrections were made. 3rd floor pending j box labeling. 2nd floor approved, 1st floor hard lid area only at corridor near entry way.
05/13/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 5-13-26: missing label at junction boxes north of room 109, missing junction box lid south of room 112. Unable to inspect above ceiling on north side of corridor because of freshly pour adhesive compound. Please reschedule.
05/14/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 5-14-26: MEP's above ceiling/ fire caulking at 1st floor corridor approved. Okay to cover progress areas.
12/09/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass Partial pass. 4th floor approved. Pending fire blocking at all top plates and near all tubs. 12/9/2025
12/10/2025 COT - HCEL - Electrical Above Ceiling  Not Ready 12/10/25: not ready for inwall inspection or above ceiling.
12/22/2025 COT - HCEL - Electrical Above Ceiling  Re-inspection required 12-22-25: rough electrical in wall /above ceiling-fire foam horizontal penetrations at party wall, add bank plates where closer than 1 1/4" from edges, finish rough in electrical from unit's 321/322 to north-awg wires must be made up at time of inspection.