Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Above Ceiling 

Permit Number - TC-COM-0125-00202

Inspection Description - COT - HCEL - Electrical Above Ceiling 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/05/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 1-5-26: 3rd floor rough electrical-328- add bank plate at party wall where awg wires are 1 1/4" from edge, 334-fire foam penetrations at decking in restroom, 325-add bank plate center near subpanel at marked location, 323-fire foam top plate penetration backside of tub. Fire foam all penetrations at party walls and at decking throughout all rooms. These items will be re-inspected at intermediates.
Note: framing inspection on any floor has not taken place and see previous notes related to 4th floor above ceiling-several rooms had already been covered with cloth material and this must be removed and a reinspection is required.
12/09/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass Partial pass. 4th floor approved. Pending fire blocking at all top plates and near all tubs. 12/9/2025
12/10/2025 COT - HCEL - Electrical Above Ceiling  Not Ready 12/10/25: not ready for inwall inspection or above ceiling.
12/22/2025 COT - HCEL - Electrical Above Ceiling  Re-inspection required 12-22-25: rough electrical in wall /above ceiling-fire foam horizontal penetrations at party wall, add bank plates where closer than 1 1/4" from edges, finish rough in electrical from unit's 321/322 to north-awg wires must be made up at time of inspection.