Inspection Status: Partial Pass

Inspection History: COT - HCBU - Building Above Ceiling 

Permit Number - TC-COM-0125-00202

Inspection Description - COT - HCBU - Building Above Ceiling 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
02/02/2026 COT - HCBU - Building Above Ceiling  Partial Pass 2/2/26: first layer of 5/8" type-x approved installation on RESILIENT CHANNEL SYSTEMS at 4th and 3rd floor ceilings approved. Ok to proceed with second layer of 5/8" type-x. Ensure all fasteners are spaced per approved plans and fasteners shall be no closer than 3/8" from edge of gypsum board and shall not penetrate more than 1/8",