Inspection History Details
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T99VL02501
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/1999 | INITIAL CODE VIOLATION | Correction Required | ADDTL COMMS - THERE WAS NO ONE HOME AT THE TIME OF INSPECTION. WITH THE EXCEPTION OF THE CLEANING OF THE FRONT YARD, THERE WAS NO EVIDENCE THAT ANY REPAIRS HAVE BEEN MADE TO THE EXTERIOR DEFICIENCIES. | |
| 10/22/1999 | INITIAL CODE VIOLATION | Violation | VIOLATION | |
| 10/06/1999 | INITIAL CODE VIOLATION | Correction Required | ADDTL COMMS - ON 9/29/99, THE TWO UNITS WERE INSPECTED. DEFECTIVE WATER CLOSET IN UNIT B. DOUBLE KEYED DEADBOLT IN UNIT B. INOPERABLE SECURITY BARS ON SOUTHEAST BED OF UNIT A. LOOSE OUTLET UNDER SINK IN UNIT B. UNIT AS COOLER AND FRIDGE ON SAME 15 AMP CIRCUIT AND KEEPS TRIPPING. TWO OUTLETS WITH OPEN GROUNDS ON UNIT AS NORTH LIVING ROOM WALL. IMPROPER SUPPLY WIRE FOR UNIT AS LIVING ROOM CEILING FAN. OPEN GROUND OUTLETS AND UNSECURED WIRE IN CARPORT. CARPORT FOUNDATION AND NORTH AND WEST WALLS ARE COLLAPSING. THE CARPORT RAFTERS ARE OVERSPANNED AND BROKEN. NO DRAIN PIPE ON TPR VALVE. THE SEWER VENT PIPE AT THE NORTHWEST CORNER NEEDS EXTENDING ABOVE THE ROOF LINE. OVERGROWN AND PREVEIOUSLY CUT VEGETATION IS A FIRE HAZARD. | |
| 10/06/1999 | INITIAL CODE VIOLATION | Violation | VARIOUS MIN |