Permit: T99PL02770

Parcel: 119033400


Addresses:

654 W 43RD ST

Inspection Status: Correction Required

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/14/2000 PLUMBING - FINAL Correction Required ADDTL COMMS - REMOVE 3/4 UNION TO RANGE AND CONNECT SOLID
01/06/2000 PLUMBING - FINAL Correction Required ADDTL COMMS - 1. NEED IRON PIPE THUR HW HEATER ENCLOSURE AND CONNECT FLEX INSIDE. 2. USE APPROVE HW HEATER VENT CAP 3. 10 LBS AIR TEST REQUIRE (SHOW ZERO).
01/06/2000 PLUMBING - FINAL Denied IVRS - Inspection 0000*
12/30/1999 PLUMBING - FINAL Correction Required ADDTL COMMS - 1. WATER HTR MUST HAVE ENCLOSURE TO PROTECT IT FROM ELEMENTS. 2. WATER HTR P&T DRAIN MUST BE STUB DOWN 6 ABOVE SLAB 3. WATER HTR GAS SHUT OFF VALVE MUST BE AGA APPROVED 4. UNDERGROUND GAS LINE FITTINGS MUST HAVE PRIMER & TAPE 5. GAS LINE MUST BE SECURED ON WALL WITH APPROVED STRAPS EVERY 8 6. GAS RANGE MUST HAVE AGA APPROVED SHUT OFF VALVE @ FLEX 7. MUST PROVIDE AIR PRESSURE TEST ON GAS LINE 10 LBS MIN. 8. YOU CAN NOT CONNECT TWO GAS FLEXES TOGETHER REMOVE ONE.
12/30/1999 PLUMBING - FINAL Denied IVRS - Inspection 0000*