Permit: T99PL01596

Parcel: 107051030


Addresses:

505 W MIRACLE MILE

Inspection Status: Correction Required

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/16/1999 PLUMBING - GAS PRESSURE TEST Correction Required ADDTL COMMS - 1. GAS PRESSURE TEST OK 2. ALL CORRECTIONS @ WATER HTRS HAVE BEEN MADE.
07/13/1999 PLUMBING - GAS PRESSURE TEST Correction Required ADDTL COMMS - 1. ENTIRE GAS LINE MUST HAVE PRESSURE TEST 10 LBS 2. UNION BY METER MUST BE REMOVED OR HAVE A GAS SHUT OFF VALVE BEFORE THE UNION 3. P&T DRAIN LINE MUST BE RUN 6 ABOVE GRADE
07/13/1999 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0000*