Permit: T99MH00639

Parcel: 140371940

Inspection Status: Correction Required

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
01/05/2000 MOBILE HOME ELECTRICAL Correction Required ADDTL COMMS - OK TO CLEAR CABLE DROP INSTALL A.C. AND RESCHEDULE.
01/05/2000 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*
12/28/1999 MOBILE HOME ELECTRICAL Correction Required ADDTL COMMS - REPLACE SOUTH ALL IN ONE PANEL WITH SUB-PANEL (ALL IN ONE IS NOT USED PER 110-3) AND I WILL NOT ACCEPT IT PER 90-4 N.E.C. ALSO NEUTRAL AND QUIP GROUNDING CONDUCTORS MUST BE ISOLATED AT THE SUB-PANEL LOCATION PER N.E.C.
12/28/1999 MOBILE HOME ELECTRICAL Denied IVRS - Inspection 0999*
12/23/1999 MOBILE HOME ELECTRICAL Correction Required ADDTL COMMS - 1. INSTALL SUB-PANEL WITHOUT METER SECTON OK FOR CABLE DROP ONLY NOT TO BE ENERGIZED TILL ITEM #1 ADDRESSED
12/23/1999 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*
12/20/1999 MOBILE HOME ELECTRICAL Correction Required ADDTL COMMS - 1. NOT READY. NO GROUND RODS OR RISER.
12/20/1999 MOBILE HOME ELECTRICAL Denied IVRS - Inspection 0210*