Inspection Status: Correction Required
Inspection History: MOBILE HOME ELECTRICAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2000 |
MOBILE HOME ELECTRICAL |
|
Correction Required |
ADDTL COMMS - 1. FLEX CONDUIT NOT ACCEPTACLE OUTDOOR AND MUST BE INSTALLED PER N.E.C. 2. ID NEUTRAL WHITE NOT YELLOW 3. MIDWEST BOX TO BE PROPERLY SECURED PER N.E.C. 4. USE HUB AND PROPER TRANSITION FROM PEDASTAL TO MIDWEST BOX 5. LABEL MIDWEST BOX THAT CIRCUIT BREAKER NEEDS TO BE SHUT OFF WHEN UNPLUGGING LOAD 1. FLEX CONDUIT REMOVED 2. MID WEST BOX REMOVED 3. INSTALLED SCH 80 PVC FROM BOX UNDERGROUND AND CONDUIT TO INTERIOR PANEL 4. INSTALLED #6 THHN PROPER COLORS. |
| 03/23/2000 |
MOBILE HOME ELECTRICAL |
|
Denied |
IVRS - Inspection 0999* |