Inspection Status: Correction Required
Inspection History: MOBILE HOME ELECTRICAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/14/1999 |
MOBILE HOME ELECTRICAL |
|
Correction Required |
ADDTL COMMS - 1. A/C CIRCUIT TOO SMALL 51.4 AMP MIN 2. INSTALL 100A MAIN FOR CIRCUIT TO FEED UNIT AT PEDISTAL 3. ITEM #1 COULD BE CORRECTED BY INSTALLING 60 FYSES AT A/C DISCO |
| 12/14/1999 |
MOBILE HOME ELECTRICAL |
|
Denied |
IVRS - Inspection 0999* |