Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/02/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE |
| 04/24/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. CONDENSATE DRAIN LINE NEEDS A TRAP AS PER MANUFACTURE SPECS 2. 40 AMP FUSES ARE TOO LARGE 35 AMP MAX 3. ANCHOR CONDENSOR TO REDWOOD SLEEPERS CORRECT AND RECALL FOR FINAL INSPECTION. |
| 04/24/2000 |
MECHANICAL - FINAL |
|
Denied |
DENIED |