Inspection Status: Correction Required
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 03/01/2000 |
ELECTRIC - UNDERGROUND |
|
Correction Required |
ADDTL COMMS - UNDERGROUND AND FINAL APPROVED |
| 02/18/2000 |
ELECTRIC - UNDERGROUND |
|
Correction Required |
ADDTL COMMS - 1. TRENCHES OK TO COVER HOWEVER SCHEDULE 40 PVC CANNOT BE USED ABOVE GROUND-RISERS INTO BOXES (NEED TO CHANGE SCH 80 OR RIGID) 2. STILL NEED PLAN TO VERIFY FIXTURES (TYPE) WHEN YOU CALL FOR INSPECTION LEAVE A MESSAGE AS TO WHERE PLANS WILL BE |
| 02/18/2000 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
PARTIAL APPROVAL |
| 02/15/2000 |
ELECTRIC - UNDERGROUND |
|
Correction Required |
ADDTL COMMS - PLEASE PROVIDE CITY APPROVED PLANS AND PREVIOUS INSPECTION REPORTS ALL TRENCHES MUST BE OPEN CONDUITS (RISERS) MUST BE PARALLED TO EACH OTHER |
| 02/15/2000 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection 0000* |