Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. INSTALL KO SEALS IN ALL OPEN J-BOXES AND DISCONNECTS 2.HAVE LICENSED ELEC L-11 CONTRACTOR HAVE GENERAL REPAIR PERMIT TAKEN OUT AND DO ALL WORK 3. NEED NEW PANEL COVERS AND PANEL SPACES 4. REPLACE ZOOA PANEL BURNING UP BUSSING BAD AND WEATHERED 5. COVER ALL OPEN J-BOXES 6. INSTALL GFC I OUTLETS WHERE OUTLETS ARE IN WORK AREAS FOR CLASS ONE DIV TWO 7. GROUND SERVICE TO BLDG STEEL 8. SECURE ALL CONDUITS PER CODE 9. ALL OVER CURRENT DEVICES TO BE SIZED PER ART 310 FOR CONDUCTORS 10. LOCATE OR INSTALL WATER BOND. 11. REMOVE ALL EXPOSED WIRING OUTSIDE 12. CONTRACTOR TO GO THRU AFTER REPAIRS AND CERTIFY IN WRITING THAT UNIT IS SAFE TO CITY 13. ALL LIGHTING TO COMPLY WITH PIMA COUNTY CODE |
| 01/05/2000 |
ELECTRIC - FINAL |
|
Denied |
DENIED |
| 12/30/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. INSTALL K.O. SEALS IN ALL OPEN J.BOXES AND DISCONNECTS. 2. HAVE LICENSED ELEC-L-11 CONTRACTOR HAVE GENERAL REPAIR PERMIT TAKEN OUT AND DO ALL WORK. 3. NEED NEW PANEL COVERS AND PANEL SPACES. 4. REPLACE 200A PANEL BURNING UP BUSSING BAD AND WEATHERED. 5. INSTALL GFCI OUTLETS WHERE OUTLETS ARE IN-WORK AREAS FOR CLASS ONE DIV 2. 6. GROUND SERVICE TO BLDG STEEL. 7. SECURE ALL CONDUITS PER CODE. 8. ALL OVER CURRENT DEVICES TO BE SIZED PER ART 310 FOR CONDUCTORS. 9. LOCATE OR INSTALL WATER BOND. 10. REMOVE ALL EXPOSED WIRING OUTSIDE. 11. CONTRACTOR TO GO THRU AFTER REPAIRS AND CERTIFY IN WRITING THAT UNIT IS SAFE TO CITY ___ ALL LIGHTING TO COMPLY WITH PIMA COUNTY CODE 7:30-8:15 AM. J.D. |
| 12/30/1999 |
ELECTRIC - FINAL |
|
Denied |
DENIED |